Recircle water temperature precision±1℃
循環(huán)水控溫精度±1℃
Flow protect
水流保護
Float level Protect
水位保護
Temperature protect: adjustable
溫度保護:可調(diào)
With the power lead, it can be connected the supply and be used as soon as.
配備電纜線,快速上電使用
With the quick connector,Easy to connect, easy to install/uninstall.
快速連接,方便裝卸
參數(shù)表
| CL0150 | |
| 電源 Power Supply | 1PH-220V/50Hz |
| 總輸入功率 W Total Power Input | 1780 |
| 制冷量 W Cooling Capacity | 3500 |
| 排熱量 W Heat Load Exchange | 4640 |
| 熱排風(fēng)量 CMF Hot Gas Exchange | 1440 |
| 冷媒 Refrigerant | R22 |
| 控溫精度 Temp Prescision | ±0.1℃ |
| 使控溫范圍 Temp Rang | 5~35℃ |
| 使用環(huán)境 Ambient Temp | 5~35℃ |
| 水流量 1/min Water Flow | 25L/min @0.22MPa |
| 最大揚程 m Max Lift | 40 |
| 水流保護l/min Flow Protect | 2 |
| 溫度保r Temp.Protect | 可調(diào) adjustable |
| 水箱容積 1 Tank Volume | 18 |
| 進出水口 Water Inlet & Outlet | RP 1/2" |
| 排水口 Drainage | RP 1/2" |
| 外形尺寸 mm DimensionWxDxH | 362x485x860 |
| 包裝尺寸 mm Dimesion WxDxH | 435x560x990 |
| 凈重 kg Net Weight | 65 |
| 毛重 kg Gross Weight | 75 |
冷水機安裝選址:
1,冷水機安裝在陰涼、干燥、通風(fēng)和太陽不能直照的環(huán)境中。
2,安裝在機柜內(nèi)時,要確保機器前面進風(fēng)不受影響及后面排風(fēng)順暢。前后距離墻壁垂直不少于60cm。
3、安裝在機柜內(nèi)時,附加風(fēng)扇的排風(fēng)量不得小于冷水機的熱排風(fēng)量。
4、安裝在封閉的環(huán)境時,對環(huán)境的換熱能力不得小于冷水機的排熱量。
冷水機保養(yǎng):
1,為保持良好的制冷系統(tǒng),冷凝器、空氣過濾網(wǎng)應(yīng)不沾有灰塵和泥土。必須定期檢查和清理。
2,冷水機如有配置水過濾器,定期檢查及更換。
3,冷水機如有配置去離子過濾器,定期檢查及更換。
4,液體計在冷水機前面,須定期檢查。液位接近或低于最警戒線應(yīng)給水箱加水。